LDC Test Results

Bramptom Sports Arena, December 2003

Kill-A-Watt 5 Step 347V HID Dimming System
21, 1000W Metal Halide Fixtures

  %output Phase Input
Voltage
(V RMS)
Ouput
Voltage
(V RMS)
Current
(A RMS)
Power
(kW)
%
saved
per
phase
%
Average
Savings
Bypassed 100% 1 343.7 343.4 20.73 6.81 - -
2 342.0 341.8 20.34 6.59 -
3 342.8 342.2 20.77 6.82 -
Line 88% 1 344.0 301.2 17.56 5.62 17.5% 19.8%
2 342.5 299.5 17.02 5.27 22.6%
3 343.2 300.0 17.11 5.49 19.4%
High 82% 1 345.0 281.7 15.55 4.96 27.2% 29.0%
2 344.4 281.4 15.09 4.64 31.9%
3 344.6 281.0 15.24 4.90 28.0%
Medium 78% 1 344.1 266.3 14.48 4.54 33.3% 35.0%
2 343.6 265.5 14.15 4.26 37.4%
3 344.1 265.7 14.18 4.48 34.2%
Low 73% 1 344.5 251.0 13.35 4.17 38.8% 40.6%
2 342.5 250.0 12.98 3.89 42.8%
3 343.3 250.2 12.99 4.07 40.2%

- Logged as using a LEM Analyst 2060 Power Meter.
- "%Output" is the percentage of input voltage supplied to the fixtures.
- All measurements except "Output Voltage" were taken at the input to the dimming system.


Light Levels at Waist Level (Lux)
Settting Bypassed Line High Medium Low
Directly under 1 lamp 829 554 467 396 340
Equidistant from 2 lamps 570 456 387 332 292
Equidistant from 4 lamps 560 436 368 316 275

Light Levels at Floor Level (Lux)
Settting Bypassed Line High Medium Low
Directly under 1 lamp 742 452 428 369 317
Equidistant from 2 lamps 560 469 398 348 298
Equidistant from 4 lamps 549 430 355 311 271

- Logged as using a LEM Analyst 2060 Power Meter.

 